0
0

A point guard I/O safety module sometimes shows the RED LED's on the input after the device has switched.  What could be the cause of this?  Set up is dual channel, equivalent with 1 second            discrepancy.  Two solenoid valves operating making 2 independent limit switches when valves closed which are wired back to the module.  Module itself has been replaced and so have both limit switches (Festo cylinder reed switches)  This does not always go into fault, only sometimes but when it does show RED LEDs' the software shows module as healthy.  Disconnecting 24v supply and reconnecting solves the problem (inputs show as amber LED).  Any help appreciated.