1756 ENBT/A Web Page Help Needed

$
0
0

I am searching the RA Site, but thought a quick post might also yield some insight.

I have a Version 17 ControlLogix L61 CPU with 1756-ENBT/A version 4 Ethernet Card.

The system is dropping communications with it's SCADA System {Archestra Wonderware 2014 R2}

I started by going to the ENBT Web Page and looking at statistics for a "smoking gun".

I think I have found some things that might be worth investegating, but am not 100% sure of what they mean.

The Diagnostic Overview shows 9/128 CIP Connections and 24/64 TCP Connections so nothing worrisome there.

However, the Diagnostic Overview also shows CIP Conn Timeouts growing at the rate of 8 per minute.  - Possible Something!!

The ethernet statistics page is where things start to get interesting.  In Errors and FCS Errors are growing at the rate of 4-6 per minute.  I have no Idea what an FCS error is? ANYONE?

I'm wondering if I need to check the PLC program for some message instructions in error state?

 