Hello everyone! Im hoping someone could shed some light on a issue im having. Im having issues with a 1794 ow8 output module. This module is used to control 8 hydraulic cylinders that push biomass into a burner. The overall problem is that roughly once every couple months a output will short in the on state and force a coil on, activating the vavle full time and burning out the coil. Each seperate output is fused on the module with a 2a fuse and each modules incoming power is also fused at 2a. The output that is shorted did not blow its fuse. The 'ON' light is not activated but 120v still runs through it. Since each valve has 2 coils and one is forced 'on' the main fuse will blow once the second half of the valve is activated because the valve is fighting itself. It is not just this one module, this happens on other modules that serve the same funtion as well. This is a contractor installed system but they have been no help so im left trying to figure it out. Could my seperate inputs be fused too high at 2a for this type of card. These are parker valves 120v 60hz with a max 1500psi pushing wet hog/chips. Any suggestions would be really appreciated!