Micro830: ARD function can not receive data

$
0
0

hello, i'm using Micro830 to receive serial data from matlab and hyperterminal. i followed article 448488 - how to read ASCII in Micro800 controller. However, ACB can receive data but ARD can not.  
Then i added a contact before ARD. Once i check and recheck it, then ARD can receive data and ACB value will be cleaned.

the 55 showed on the ARD is the value from previous buffer

774484280.thumb.jpg.fe2e27cb1895ce39202c

 

1898356829.jpg

703006989.jpg

1898356829.jpg

2026657297.jpg


How to Select suitable FactoryTalk Licence

$
0
0

please help me to Select suitable FactoryTalk Licence 

1-FactoryTalk SE can make program to HMI (PanelView) or not? 
1.1- if yes that me i need to buy (FactoryTalk View Site Edition Station 15 Display)? 

2- when selecting licence to i see it depend on no. of display that is mean ?(FactoryTalk View Site Edition Station 15 Display) use to make No, 15 screen on my program ? 
2.1- how many tag in each screen ? 

3- in factorytlak ME (FactoryTalk View Machine Edition Station Runtime 15 Displays) used only to put programm in PC NOT put in HMI(PanelView)? 
3.1- if only for PC what is max tag can i put on HMI(PanelView)

3.2- if i want increase no. of tag of HMI i need buy licence and what is this license 

New to PLC's

$
0
0

Hello,

I am sorry I am sure this has been asked before but I did some searching and didn't find much. I have no experience with PLC's and my manager has suggested I take some classes to fill a void in our team's skill set.  We use Allen Bradley PLC's and have a seat of RSlogix5000.  I hope to learn how to modify existing programs for some of our test equipment.  I want to add sensors to some existing test equipment and record data generated by these sensors.  My question for this group is If you were just getting started and you had a budget for a week of training what classes would you take? Where would you take them?  My manger and I realize a week of training may barely scratch the surface.  Is Allen Bradley's training worth the time and money for travel?  Is there local 3rd party training I can find in the Cleveland area that teaches RSlogix5000?    

I am thinking about the below courses.

CCP146 Conrtol Logix 5000 System Fundementals

http://literature.rockwellautomation.com/idc/groups/literature/documents/pp/gmst10-pp185_-en-e.pdf

and CCP 151 Basic Ladder logic

http://literature.rockwellautomation.com/idc/groups/literature/documents/pp/gmst10-pp189_-en-e.pdf

 

Also what is the difference between RSlogix 5000 and RSlogix 500? 

pv plus 400

$
0
0

Hi

     I have pv plus 400 HMI. I want to take backup from the hmi. I want to set IP address in settings. I want to go to configuration mode. How do i go to configuration mode. Please help me.

Comms Monitoring of SCADA

$
0
0

Forum Members,

Time for a silly question.

I have an L33ER based system that is talking to a PC SCADA software called Ignition by Inductive Automation.  Not really asking about Ignition, but rather how to monitor in the PLC whether or not the communications is working properly. For a majority of Rockwell's products (on E/IP) you would simply add the module and generally there is a tag in the AOP or do a GSV on the Module.  Since this is a PC based SCADA, I'm a little lost trying to figure out how to monitor communications and availability.

Is the solution to create a Generic EtherNet Module, but I really don't think there is configurable instances or sizes of instances.

Ideas on what I should be thinking about or looking for?

 

Thanks,

Rick

5/04 Rebooting intermittenly

$
0
0

Hello all, I have problem with a 5/04 shutting down and restarting intermittenly on piece of equipment at work for a week now.

It seems to happen when the machine starts and stops more often versus running steady.

When I looked at the program that was being ran It had a major fault listed in errors, that was for an output card not being the same as what was listed on the I/O of the program.

I replaced the PV550 to PVP600 over a month I don't know if it would be a comm issue causing this, but I would think that would happened right after install.

Retrive Password from mer file

$
0
0

Is there a possiblity to retrive password from mer file?
I wanted to restore mer to runtime with local directory and its asking me for password that i don't have. 
Could some one help?
 

Capture.PNG

Capture2.PNG

Wonderware and rslinx support windows 10

$
0
0

Good day, Hi guys

Does anybody know about the wonderware 10.1 and RSlinx classic

I want to ask whether wonderware 10.1 and RSlinx classic 2.55 do not support on windows 10?

which version can support windows 10 give me link please?

Thanks for help


Micrologix 1500 1761-Net-Aic+ Issues

$
0
0

A customer of mine has a ML 1500 LRP connected to a Net-AIC+ via the mini din connector (CH 0 of plc to port 2 of AIC) from this AIC then connects a a bunch of other networks via Port 1. This is all working fine. The PLC port is configured as DF-1

My issue is that I need to connect to the PLC and view the code online. I cannot do this because the machine cannot run without the devices connected via the AIC to Ch 0 of the PLC. I have come to the conclusion that I need the LSP to do this easily. However, they had another AIC+ here already. Thought it would be a simple hookup but I cannot get it to work. 

I have connected them together via port 3 with the proper wiring. Not showing any errors and the status lights flashing as they should. I cannot connect to the PLC through this though. Have tried the following combinations. 

1761-CBL-PM02
Null Modem Cable 
with RS-232 to usb converter. Both cables are good because I can connect to the PLC with the PM02 cable directly on the PLC and the Null Cable if I pull the existing cable off of the first AIC+ and plug it into Port 1

I have also tried connecting with my 1747-UIC and it does not work. 

Is this combination even possible. Im guessing the issues are related to the PLC port being configed as DF-1 and this not being able to be passed to the second AIC+ 

Any help would be appreciated. I will get the LRP but dont want to wait a few days when I feel like I could have this solved now

Editing Device in KEPServerEx for ControlLogix

$
0
0

We're running KEPServerEx 4.5 with the AB drivers to interface with a Siemens WinCC HMI.
All we've done is change the L61 processor with an L72 and then KEP shows the incorrect values for the tags. We stick the L61 back in and all is okay.

The Device properties haven't changed as the L72 is part of the ControlLogix 5500 family. The IP address is the same as well as the project name, etc.
I've checked the properties against the KEP manual and all is okay. The manuals I have don't mention editing a device in KEPServerEx.

I feel we've missed something. :hmmm:

Any thoughts?

Add pause botton Allen bradly SLC5/03

$
0
0

hello guys, I've got a project and i am not too familiar with the allen bradley PLCs. So I hope you guys can help me with some ideas. we have a palitazer in our class we have to modify the PLC's program and add an extra fisical bottons, pause botton(red botton) and continue botton(green botton) 

some times the operator needs to get inside to the enclosure WHILE THE MACHINE IS IN AUTO MODE and that is why we need the stop botton, so the operator can push it and "pause" the machine in any moment. all the outputs and inputs should stay in their current state until the operator press the start/continue bottom, after this the machine should be able to continue the routine. 

here is some info about the palletizer 

http://bidonequipment.info/pdf%20files/FMC%20CORPORATION%20EZY-150%20Palletizer.pdf

I dont know if this is possible or not I've been studyng the ladder, but I could find the solution. 

I atached the PLC program in this file, thanks you very much

we got the PLC Allen Bradley SLC 5/03 

How can I use Temporary End (TND) can this help?

 

if somebody want to see the PLC program (ladder) just let me know

Micrologix 1100 and stepper drive

$
0
0

Hey guys, 

Really in a pinch here, our stepper drive seems to have somewhat died..... IIhave output pulses going from the micrologix 1100 to the +step but nothing is moving. I can connect to the sure  step program and move in test mode and scl. 

 

I need this machine running for Wednesday, is there any way someone can give me an example of how to send serial commands to the drive? It's  something I have done yet (still relatively new to this) but if I could get some basic commands going, I'm sure I can make with the bags bones system to the drive arrives

AB

$
0
0

Hi, I have a question related to installation of RSlinx software. I already installed the software on my pc. But i cant able to open the software. So, i try to uninstall the software. I cant able to uninstall the software during uninstall its shows the message that "fatal error during installation". How to rectify the problem.

1756-OF6CI output card - broken wire signal or equivalent?

$
0
0

Good afternoon Mr.PLC forum members.

 

We recently had a fuse blow on the wiring between a 1756-OF6CI analog out card and a control valve (which we have no feedback for - only the 0-100% output). Took a little longer to troubleshoot since we have no feedback and we also don't monitor individual channel status of the card. For input cards (1756-IF8H or IF16H), it's easy enough to use the under-range/over-range or broken wire signal to troubleshoot a blown fuse or bad connection, and activate an alarm. I have been told by our local consultant-technician that there is an equivalent monitoring bit for output cards. Reading the instruction manual for the 1756-I/O cards, the fault channel bits do not seem to have this type of function for the 1756-OF6CI. The fault bits only seem to look at the requested output values, and at the connection between card and PLC itself as far as I can tell.  Am I missing something?

 

thanks for your help

Homing Axis help required!

$
0
0

Hi all,

I have the following system and need your advice and thought on how to do homing for this system, it is not hard thing but for me it is because this is the first time i work with motion and therefore your support will be really helpful.

I have guard logix controller with Power flex 527 drive with its incremental encoder, Absolute encoder 842E-CM-M those connected via Ethernet switch and two proxy sensors connected to Point IO DI safety used to confirm homing is done.

what I need to do, is to figure out what is homing procedure for this system, I read through MAH instruction and it is possible to use it if I have limit switch connected to Drive DI ch1 which will need to configured for home, but I dont have this limit switch.

is there any alternative way to do the homing? 


Micrologix 1400 HSC Issue

$
0
0

Looking for help,

Have a Micrologix 1400, 1766-32BXBA. Using the Function file, configured HSC:4 to count pulses coming in on input I:0/6 and set the OMB to decimal 128, to turn on output O:0/7 when the High Preset is reached. The accumulator counts up fine, resets at the preset of 955, then counts up again but output O:0/7 does not turn on when the High Preset is reached. Any assistance will be greatly                 appreciated.

HSC:4 Configuration:  PFN=9, FE=1, AS=1, CE=1, CU=1, MOD=0, HIP=955, LOP=(-)2147483648, OVF=2147483647, UNF=(-)2147483648, OMB=128

Rest of configuration parameters are set to "0"

PLC 2 files?

$
0
0
Hi all, I just got an e-mail from my big boss about .PR1 and .DA1 files. I think that the files come from an Allen Bradley PLC 2, but can someone confirm. Now for the good bit. How can I open these files? I take it that the PLC 2 worked on a DOS programming enviroment. I have 5, 500 and 5000 software. Thanks Conor

Fault Code 80

$
0
0

I am working with a CompactLogix 5330 and am getting the fault code on the devicenet scanner 00 80 and am unsure on what to do.  I know that 80 means that the controller is in idle mode but I have the key switch in run.  Any help will be appreciated.  Thank you.

Micrologix 1200 PLS Configuration

$
0
0

Hello Everyone,

Is there anyone on this forum who has successfully configured the PLS  function on any of the Micrologix controllers. I have a Micrologix 1200 and configured the PLS for a 3 element function, following the example in Chapter 5 of the Reference manual as follows ; HSC:0 MOD = A00, HSC:0.OMB = 768, HSC:0.HPO = 768

PLS10:0, HIP = 250, OHD = 0000  0000  0000  0000

PLS10:1, HIP = 500, OHD = 0000  0001  0000  0000

PLS10:2, HIP = 1000, OHD = 0000  0010  0000  0000

Connected encoder and applied pulses continuously. First go round, HSC:0.ACC counts up to 250, then resets to 0, counts up to 500, then resets to 0, counts up to 1000, then resets to 0. This sequence just keeps repeating over and over and is causing very erratic  action on the selected outputs(Output 8 and 9). The outputs are turning on and off but not at the accumulator counts that I expected.  Any ideas as to what may be wrong will be greatly appreciated, Thank you

Wonder ware Intouch vs FactoryTalkview ME

$
0
0
I am currently working on a project and was wondering what everyone's option of the Wonderware Intouch product is vs The Rockwell FactoryTalkView ME. I currently run FTV and I feel its just ok. I have a new project where I can run the Wonderware product it looks great but I'm not sure about ease of programmability, and if it is user friendly compared to FTV. So let me know what you think.