Good morning all -
I have a Flex I/O 1794-IE8 that the raw counts are varying by about 30 with no change in input. It is used as a 4-20 mA input, reading the output from a signal conditioner from a LVDT. This is the only input used in this module. The stackup for the Flex system is a 5434 CPU (with Ethernet and DeviceNet cards), 2 - 1794-IB16 input modules, 1 - 1794-OB16 output module, 1 - 1794-OW8 relay module and the 1794-IE8 analog input at the end of the line.
I have checked the wiring to ensure it was as specified in the installation instructions. The LVDT and signal conditioner was changed to see if the problem moved, but it didn't. Input 1 is used on the IE8, other inputs were also tried, with no change in results. I tried connecting the output of the signal conditioner to a spare MicroLogix 1400 and a 1762-IF4 analog card in a further attempt to isolate the problem. The MicroLogix raw count reading was rock steady, while the IE8 was still fluctuating. I have seen some references online to other instances of issues similar to this, is it a known issue with these modules? It appears that the IE8 is the problem, but I hate to pay to replace it with another if this is a known issue with the IE8 cards.
As another observation, the raw counts coming from the MicroLogix were substantially different from the Flex, like 10258 Flex vs 14541 Micro. I had considered reading the conditioner with the Micro and messaging the count to the Flex. The Flex is communicating with a drive via DeviceNet, and I would rather not tackle exchanging the Flex at this time. Thus the thought of using the Micro to send the Flex a stable count value. What would cause the raw counts to be so much different?
Thanks for reading...