Hi all,
Did a quick search in the forum to see if this has been asked before but couldn't see anything jumping out.
I have what appears to be an issue in making a third party RTU using a DF1 enabled RS232 port talk to a PLC5.
Background: The device talks seamlessly to a SLC500 with the CH0 set up as a standard DF1 Slave. I have replicated the setup like for like on the PLC5, I'm also happy that the cable between (the 25Way Sub) is as it should be.
Problem is, no data exchanges are happening, none of my PLC values are registering. The COMM light on the PLC5 is flickering periodically (almost as if its trying to periodically service a request from the master) but then times out. The RTU is scanning one N31 and one N32 integer so really small.
I recall (10 years or so ago) that when using a different telemetry device (Serck 2000M with PR27 DF1 card) I had to specifically set the PR27 to read PLC5 registers over SLC500 ones. This suggests that maybe there is an inherent difference between a PLC5 NRegister and a SLC500 NRegister??
I do not have the availability of setting my new RTU to scan PLC5 type registers so this may mean I am going back to the vendor. Before I do I was wondering if anyone here had come across this before?
Any advice would be awesome
Thanks
Alex